E+H Ultrasonic Level Transmitter FMU4X Error Code List

The E+H ultrasonic level transmitter FMU4X series is widely used in industrial level measurement, and its self-diagnostic function indicates fault types through error codes. This article compiles common error codes, descriptions, and solutions for reference by engineering and technical personnel and procurement staff.

E+H Ultrasonic Level Transmitter FMU4X

Error Code Classification and Solutions

Error codes are divided into two categories: Alarm (A) and Warning (W). Alarms usually require immediate action, while warnings indicate potential problems. The following are listed in code order.

A101, A102, A110, A152, A160

  • Error Description: Diagnostic error
  • Solution: Reset; if the alarm persists, replace the circuit board.

W103

  • Error Description: During initialization
  • Solution: If the alarm message does not disappear within a few seconds, replace the circuit board.

A106

  • Error Description: During download
  • Solution: Wait for the download to finish and the message will disappear.

A111, A113, A114, A115, A121, A125, A155, A164, A171

  • Error Description: Circuit board fault
  • Solution: Reset; monitor the system's electromagnetic compatibility (EMC), improve if necessary; if the alarm persists after reset, replace the circuit board.

A116

  • Error Description: Download error
  • Solution: Check the connection and download again.

W153

  • Error Description: During initialization
  • Solution: Wait a few seconds; if the error persists, power off and then power on again.

A231

  • Error Description: Sensor fault
  • Solution: Check the connection; if necessary, replace the HF module or circuit board.

A281

  • Error Description: Temperature probe open circuit
  • Solution: Replace the sensor.

A502

  • Error Description: Sensor model not detected
  • Solution: Replace the sensor and/or circuit board.

W511

  • Error Description: No factory calibration
  • Solution: Perform factory calibration.

A512

  • Error Description: During curve recording
  • Solution: The alarm disappears after a few seconds.

A521

  • Error Description: New sensor model detected
  • Solution: Reset.

W601

  • Error Description: Linearization curve not monotonic
  • Solution: Correct the data table (enter a monotonically increasing data table).

W611

  • Error Description: Fewer than two linearization points
  • Solution: Enter more data pairs.

W621

  • Error Description: Simulation function on
  • Solution: Turn off the simulation function. Go to the "Output" (06) function group, "Simulation" (065) function.

E641

  • Error Description: No usable echo
  • Solution: Check basic calibration (see page 21).

E651

  • Error Description: Level within safety distance, risk of overflow
  • Solution: The error disappears when the level leaves the safety distance; a reset may be required. Lock the "Safety Settings" (01) function group, "Confirm Alarm" (017) function.

A661

  • Error Description: Sensor temperature too high
  • Solution: Check the medium temperature or inspect the sensor.

A671

  • Error Description: Linearization incomplete
  • Solution: Activate the linearization table.

W681

  • Error Description: Current out of range
  • Solution: Perform basic calibration and check linearization.

W691

  • Error Description: Noise detected, level ramp activated
  • Solution: Check the process conditions and eliminate noise interference.

Quick Reference Table of Common Error Codes

Code Type Description Solution
A101AlarmDiagnostic errorReset; if persists, replace circuit board
A102AlarmDiagnostic errorReset; if persists, replace circuit board
A110AlarmDiagnostic errorReset; if persists, replace circuit board
A152AlarmDiagnostic errorReset; if persists, replace circuit board
A160AlarmDiagnostic errorReset; if persists, replace circuit board
W103WarningDuring initializationIf not disappearing within a few seconds, replace circuit board
A106AlarmDuring downloadWait for download to finish
A111AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A113AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A114AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A115AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A121AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A125AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A155AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A164AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A171AlarmCircuit board faultReset, check EMC, replace circuit board if necessary
A116AlarmDownload errorCheck connection, download again
W153WarningDuring initializationWait a few seconds, power off and restart
A231AlarmSensor faultCheck connection, replace HF module or circuit board
A281AlarmTemperature probe open circuitReplace sensor
A502AlarmSensor model not detectedReplace sensor and/or circuit board
W511WarningNo factory calibrationPerform factory calibration
A512AlarmDuring curve recordingDisappears after a few seconds
A521AlarmNew sensor model detectedReset
W601WarningLinearization curve not monotonicCorrect data table
W611WarningFewer than two linearization pointsEnter more data pairs
W621WarningSimulation function onTurn off simulation function
E641ErrorNo usable echoCheck basic calibration
E651ErrorLevel within safety distance, risk of overflowLevel leaves safety distance, may need reset
A661AlarmSensor temperature too highCheck medium temperature or inspect sensor
A671AlarmLinearization incompleteActivate linearization table
W681WarningCurrent out of rangePerform basic calibration, check linearization
W691WarningNoise detectedCheck process conditions, eliminate noise interference

Maintenance Recommendations

  • Regularly check the connection between the sensor and circuit board to ensure good contact.
  • When an alarm occurs, first try resetting; if it cannot be eliminated, then consider replacing components.
  • Pay attention to electromagnetic compatibility (EMC) to avoid false alarms caused by interference.
  • For warning codes, address them promptly to prevent them from escalating into alarms.

The above code table can help quickly locate faults in the E+H ultrasonic level transmitter FMU4X and improve maintenance efficiency. For more detailed guidance, please refer to the product manual.