Product family:
Tuning fork level switch
Tuning fork level switch
Liquiphant FTL51B;Approval NEPSI Ex db IIC T6 Ga/Gb;Output FEL64, relay DPDT 19-253VAC/19-55VDC contact 253V/6A + test button;Display/Operation W/o; switch;Housing/Material Single compartment; Alu, co
Order Code:FTL51B-NCA4ABFAA2CJI1VBJ+LA
Name:Liquiphant FTL51B
Configuration
| Code | Name | Order | Specification |
|---|---|---|---|
| 010 | Approval | NC | NEPSI Ex db IIC T6 Ga/Gb |
| 020 | Output | A4 | FEL64, relay DPDT 19-253VAC/19-55VDC contact 253V/6A + test button |
| 030 | Display; Operation | A | W/o; switch |
| 040 | Housing; Material | B | Single compartment; Alu, coated |
| 050 | Electrical Connection | F | Thread M20, IP66/68 NEMA Type 4X/6P |
| 060 | Application | A | Process max 150oC/302oF, max 64bar |
| 080 | Surface Refinement | A | Standard Ra<3,2µm/126µin |
| 085 | Type Of Probe | 2 | Tube extension |
| 090 | Sensor Length; Material | CJ | ..... mm L, Ra<3,2um/126uin; 316L |
| 105 | Process Connection, Sealing Surface | I1 | Thread ISO228, G |
| 110 | Process Connection | VBJ | 3/4", 316L |
| 590 | Additional Approval | LA | SIL |
Configuration Explained
This is an FTL51B vibrating level switch, with NEPSI explosion-proof approval and CCC marking, usable in hazardous areas, 3/4 inch process connection, 316L, FEL64 relay output, DPDT, 19 to 253 VAC or 19 to 55 VDC, contact 6 A, with test button, press the button on site to verify operation, flexible alarm settings with multiple stages, suitable for level interlock in hazardous area liquid tanks.