Instrumentation · Engineering · Package · PLC
0755-82221901 sales@ainstru.com

FTL51H Liquiphant M

FTL51H Liquiphant M
Liquiphant M FTL51H
Configurable Models 7 models
Liquiphant FTL51H is a point level switch with extension tube for use in hazardous areas with all international certificates. Especially useable in the food and life sciences industry with hygienic certificates (3-A, EHEDG, ASME BPE). FTL51H offers functional safety SIL2/SIL3. Reliable measurement values, not affected by: changing media properties, flow, turbulences, gas bubbles, foam, vibrations or build-up.
Compare

Density

Measuring Principle Vibration Density
Characteristic / Application Premium device for density measurement in hygienic/aseptic applications.
Focus Food & Beverage and Life Sciences.
Sensor with pipe extension up to 3 m (9,85 ft).
Modular housing or completely welded compact housing.
Wide range of certificates.
Supply / Communication via density controller FML621
Ambient temperature -40 °C...70 °C (-40...158 °F)
Process temperature 0...80 °C (32…176 °F)
Process pressure 0...25 bar (0…362 psi)
Wetted parts 316L
Hygienic 3A
EHEDG
Sensor length Short tube (Liquiphant II)
148mm…3000mm (6,00…118")
Output Pulse
Certificates / Approvals ATEX, FM, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI
Specialities Density/Concentration measurement in combination
with density controller FML621,
Surface finish: mechanical polished (up to 0.3 µm)
Components Density Computer FML621

Point Level / Liquids

Measuring Principle Vibration Liquids
Characteristic / Application Premium device for point level detection
in hygienic/aseptic applications.
Focus Food & Beverage and Life Sciences.
Pipe extension up to 3 m (9,85 ft).
Modular & completely welded housing concept,
Wide range of certificates.
Specialities Plug and play functionalities,
Surface finish: mechanical or electro-polished,
Density/Concentration measurement,
SIL 2/3 according to IEC 61508
Supply / Communication PROFIBUS PA,
19 ..253V AC,
10...55V DC-PNP,
19...253V AC or 19...55V DC with relay DPDT,
8/16mA,
NAMUR,
PFM
Ambient temperature -50 °C...+70 °C
(-58 °F...+158 °F)
Process temperature -50 °C...+150 °C
(-58 °F...+302 °F)
Process pressure / max. overpressure limit Vacuum...64 bar
(Vacuum...928 psi)
Min. density of medium 0.5g/cm³
(0.4g/cm³ optional)
Main wetted parts 316L
Process connection Threads (for weld-in adapter):
G3/4A, G1A,
Flange:
DN25...DN100,
ASME 1"...4",
JIS 25A...100A
Process connection hygienic Tri-Clamp,
DIN 11851, DIN11864-1
Ingold,
Flush mount,
DRD,
SMS1145,
Varivent (Varinline)
Sensor length Short tube (Liquiphant II)
148mm…3000mm (6,00…118")
Communication PROFIBUS PA
Certificates / Approvals ATEX, IEC Ex, FM, CSA C/US, TIIS,
INMETRO Ex, NEPSI Ex
Safety approvals Overfill protection WHG,
SIL 2/ SIL 3
Design approvals Inspection certificate 3.1, EN10204,
CoC ASME BPE,
Conformity to cGMP,
EU Food Contact Material (EC) 1935/2004,
US Food Contact Material FDA CFR 21,
CN Food Contact Material GB 4806,
Declaration of Conformity ASME B31.3,
AD2000,
CRN approval
Hygienic approvals 3-A,
EHEDG,
CoC-ASME BPE
Marine approval GL/ ABS/ DNV
Options Customized settings (Density)
Components FTL325P/FTL375P Interface PFM
FTL325N/FTL375N Interface NAMUR
Successor FTL63

The Liquiphant FTL51H vibronic point level switch with extension tube can be used in hazardous areas and has various international approvals. With hygienic certifications such as 3-A, EHEDG and ASME BPE, it is especially suitable for the food and life sciences industries. The FTL51H achieves SIL2/SIL3 functional safety, and the second line of defense ensures the highest degree of device safety and availability. The measured value is stable and unaffected by flow, turbulence, bubbles, foam, vibration, solids content or buildup.

 

Benefits

Suitable for safety systems requiring SIL2/SIL3 functional safety, in accordance with IEC 61508/IEC 61511-1

Various process connections available

Various electronic inserts, such as NAMUR, relay, semiconductor thyristor, PFM signal output, for connection to various process control systems

Also available with PROFIBUS PA communication protocol

No calibration required: fast and economical device startup

No mechanical moving parts, no maintenance, no wear and a long service life. Fork damage can be monitored to ensure proper function

FDA-listed material (PFA Edlon)

 

Application areas

Limit switch with electropolished surface, for detection of all types of liquids.

Process connection: thread, flange and hygienic connections (clamp, milk coupling, aseptic, DRD, SMS, Varivent)

Temperature: -50 ~ +150 °C (-58 ~ +302 °F)

Pressure: -1 ~ +64 bar (-14.5 ~ +928 psi)

Sensor material: 316L

International explosion protection approval, WHG overflow protection, SIL, hygienic approval, marine approval

Spare Parts & Accessories 63

63 spare parts · click to collapse
Order codeDescription
52002698Aluminum coverO-ring EPDM for Aluminium housing F13, Ex dDetails
52002699Aluminum coverO-ring EPDM for Aluminium housing F17Details
52005266Stainless Steel CoverFor stainless steel housing 316L. Liquiphant M.Details
52006903Aluminum coverO-ring EPDM for Aluminium housing Liquiphant M/S, Liquicap M, Soliphant MDetails
52025606plastic coverGasket EPDM Polyester housingDetails
52025790Transparent coverGasket EPDM Polyester housingDetails
52027000Stainless Steel CoverGasket 67,5x2,9x1,5 VMQ/PTFE Stainless steel housing F15Details
52027002Window cover with gasketSight glass: glass Gasket 67,5x2,9x1,5 VMQ/PTFE Stainless steel housing F15Details
52028207Window cover with gasketSight glass: Polycarbonat PC Gasket 67,5x2,9x1,5 VMQ/PTFE for use in non-hazardous area (EEx ia) Stainless steel housing F15Details
52004236AdapterFixing set, consists of: securing ring 301 adapter ring PPA Liquiphant M/Liquiphant SDetails
52004137O-ringCover seal set Polyester housing F16Details
52004277Seal kitconsists of: 10x O-ring 70,0x3,0 EPDMDetails
52008495Seal kitfor coverDetails
52028179gasketProfile gasket for cover Stainless steel housing F15Details
516734-1000Plug connector ISO 4400, 3-pole, NPTF 1/2, PEGasket + screw.Details
516734-2000Plug connector ISO4400 DIN43650 3+PE Pg11Gasket + screw. Usage: FTL50/FTL50H/FTL51/FTL51H.Details
52002447cable entryconsists of: adapter M20 > G1/2, 304 gasket NBR blind plug G1/2 Cerabar M, Liquiphant MDetails
52002448cable entryconsists of: adapter M20 > NPT1/2, 304 gasket NBR plug NPT1/2 Cerabar M, Liquiphant MDetails
52002450cable entryconsists of: adapter M20 > Pg13.5, 304 gasket NBR blind plug Pg13.5 Cerabar M, Liquiphant MDetails
52004133Adapterfor Polyester housing F16Details

Configurator / Comparison

ConfigureEnter a product model to configure
CompareEnter the product models to compare — up to three products

   

   

 

 

Source: public information from the Endress+Hauser website

Measuring principle video

Click to play
7 models · click to collapse
All documents for this model
11 documents · click to expand
BA

Liquiphant M/S FTL50, FTL51, FTL50H, FTL51H, FTL51C, FTL70, FTL71 Electronic insert FEL50A PA English

40 pages
Preview
BA

Liquiphant M FTL 50 H, FTL 51 H Instruction Manual English

32 pages
Preview
BA

Liquiphant M FTL 50 H, FTL 51 H Instruction Manual English

32 pages
Preview
TI

TI 焊接接头、过程转接头和法兰 Chinese

Rev. 2726 130 pages
Preview
TI

技术资料 Liquiphant M FTL50(H), FTL51(H) Chinese

Rev. 1515 56 pages
Preview
TI

技术资料 Liquiphant M FTL50(H), FTL51(H) Chinese

Rev. 1412 52 pages
Preview
TI

技术资料 Liquiphant M FML621 Chinese

Rev. 1312 36 pages
Preview
TI

TI Weld-in adapter, process adapter and flanges English

Rev. 2726 132 pages
Preview
TI

Liquiphant M FTL50, FTL51, FTL50H, FTL51H Technical Information English

Rev. 1820 52 pages
Preview
TI

Technical Information Liquiphant M Density and Density Computer FML621 English

Rev. 1312 36 pages
Preview
TI

Liquiphant M Density FEL50D Technical Information English

Rev. 0209 40 pages
Preview
Municipal Wastewater Treatment

Municipal Wastewater Treatment · tuning fork — Application Case

Site Conditions

This is a Municipal Wastewater Treatment customer whose plant is at the inlet, biological and outlet stages of a municipal plant. The main task was vibrating-fork point level detection and high/low alarms.

The Problem

The difficulty lies in high solids and corrosive fractions, with large diurnal flow swings; at the same time effluent parameters drift and probes foul with sludge and biofilm. Specification therefore means choosing fork length and surface finish by density and stickiness.

What We Did

We took a level range approach — level solution matched to the actual tank and silo geometry. Delivery was built around choosing fork length and surface finish by density and stickiness, with point-by-point checks on: stable compliance with Grade 1A discharge limits and online data reporting.

Operating Outcome

In service the system performs as intended — no calibration needed, with dependable switching, with routine maintenance falling noticeably.

Food & Beverage

Food & Beverage · tuning fork — Application Case

Application Context

dosing, pasteurising, filling and CIP stages is a typical Food & Beverage duty. The project started from tuning fork, focusing on vibrating-fork point level detection and high/low alarms.

Process Constraints

frequent cleaning demands instruments that withstand hot CIP/SIP caustic cycles, and syrups, dairy and beverages that scale easily, under strict hygienic requirements only amplify it. The tuning fork specification must therefore cover choosing fork length and surface finish by density and stickiness.

Delivery Approach

Delivery was handled as the level range — level solution matched to the actual tank and silo geometry. Execution centred on choosing fork length and surface finish by density and stickiness, together with food-safety and hygienic design per 3-A / EHEDG.

Field Results

Operation shows the benefit clearly — no calibration needed, with dependable switching, with confidence in this measuring point improving markedly.

Chemical & Pharmaceutical

Chemical & Pharmaceutical · tuning fork — Application Case

Customer Profile

The typical setting in Chemical & Pharmaceutical is reactors, metering vessels and finished-product tanks. The measuring point is tuning fork; the focus is vibrating-fork point level detection and high/low alarms.

Key Difficulties

Conditions are highly corrosive media with solvents and crystallisation, partly in explosive atmospheres and, on top of that, corrosion plus Ex protection shortens instrument life and makes downtime costly, which a standard configuration cannot handle for long. The design therefore starts with choosing fork length and surface finish by density and stickiness.

Implementation

The scope ran through the level range: level solution matched to the actual tank and silo geometry. Technically it hinges on choosing fork length and surface finish by density and stickiness, and on these requirements: Ex certification and GMP traceability of records.

Customer Benefit

In practice this means no calibration needed, with dependable switching, which cut the workload on the site maintenance team.

Power & Energy

Power & Energy · tuning fork — Application Case

Project Background

The project covers boiler feedwater, turbine condensate and FGD/DeNOx systems. The work centres on tuning fork and the core task is vibrating-fork point level detection and high/low alarms.

Operating Challenges

The medium and duty are characterised by high temperature and pressure with both steam and saline water, and drift under high temperature and pressure, with very costly unplanned outages. So tuning fork cannot be specified generically — it calls for choosing fork length and surface finish by density and stickiness.

Solution

The Ainstru engineering team worked through the level range: level solution matched to the actual tank and silo geometry. The configuration involves choosing fork length and surface finish by density and stickiness, with these requirements in view: compliance with power-industry codes and unit availability targets.

Results

Since start-up the system has run steadily; the practical result is no calibration needed, with dependable switching.