Instrumentation · Engineering · Package · PLC
0755-82221901 sales@ainstru.com

HI8931DN

HI8931DN
Panel Mounted Conductivity Controller
Panel mounted conductivity controller 0.0-199.9 µS/cm. Hanna’s mid-range controllers offer economical, constant monitoring of pH, Oxidation Reduction Potential (ORP), Electrical Conductivity (EC), and

Overview

Panel mounted conductivity controller 0.0-199.9 µS/cm. Hanna’s mid-range controllers offer economical, constant monitoring of pH, Oxidation Reduction Potential (ORP), Electrical Conductivity (EC), and Dissolved Oxygen. The compact, easy-to-use controllers are designed to consistently perform in most environments and conditions twenty-four/seven.

An analogue controller can be configured by you to your exact process requirements. There is no need to worry about space or cost, as all the controllers can be installed in confined spaces and the low cost means previously manual monitoring can now be automated, saving time and money. HI-8931DN Conductivity Controller (Range 0.0 to 199.9 μS/cm) A simple panel mounted conductivity controller designed for easy operation.

The HI-8931 range should be used with the HI-8936 transmitter series. Using the correct transmitter will ensure a strong, interference-free signal at a distance of up to 300 metres (1000 feet). The output configuration for connecting a recorder or a PLC can be chosen between 0-20 or 4-20 mA.

Use a HI-7135 electrode for in-line applications or the HI-7638 with external threads for tanks. The electrodes contain a built-in NTC sensor for temperature compensated conductivity measurements. The controllers have large, easy-to-read displays, fire-retardant casing, electrode input, automatic alarm features, recorder output, plus dosing consent feature on ORP and pH models.

The front panel is protected behind a transparent splash-proof cover. Order Information: The HI-8931 series is supplied with mounting brackets and instructions.

Specifications

ParameterValue
SKUHI8931DN
EC RangeHI-8931AN: 0.0 to 199.9 mS/cm HI-8931BN: 0.00 to 19.99 mS/cm HI-8931CN: 0 to 1999 µS/cm HI-8931DN: 0.0 to 199.9 µS/cm
EC ResolutionHI-8931AN: 0.1 mS/cm HI-8931BN: 0.01 mS/cm HI-8931CN: 1 µS/cm HI-8931DN: 0.1 µS/cm
EC Accuracy±2% F.S. (excluding probe error)
EC Calibrationmanual, two point, through offset and slope trimmers
EC/TDS Temperature Compensationautomatic, 0 to 60°C with β=2%/°C; see also transmitter HI-8936
Input ChannelsDIN (probe) or 4-20 mA (transmitter)
EC/TDS ProbeHI-7635 for in-line applications or HI-3001D for flow-thru (not included)
Alarm Relay RangeHI-8931AN: 0.0 mS and 100.0 mS HI-8931BN: 0.00 mS and 10.00 mS HI-8931CN: 0 µS and 1000 µS HI-8931DN: 0.0 µS and 100.0 µS
Dosing ControlOFF/AUTO/ON with selection switch
Over Dosing Controladjustable, from 5 min to 60 min at front or disable by wire strap - on rear panel
Digital Input SignalHI-8931AN: HI-8936A / A HI-8931BN: HI-8936B / BL HI-8931CN: HI-8936C / CL HI-8931DN: HI-8936D / DL
Backlightcontinuous on
Enclosureflame retardant ABS body and front panel; transparent splash-proof front cover
Panel cut out141 x 69 mm (5.6 x 2.7”)
Recorder Output0 to 20 mA or 4 to 20 mA (isolated)
Set Point1, Isolated, 2A, max. 240V, resistive load, 1,000,000 strokes; range: 0.0 to 199.9 mS/cm; 0.00 to 19.99 mS/cm; 0 to 1999 µS/cm; 0.0 to 199.9 µS/cm
Power Supply230 VAC ±10%; 50/60 Hz
Environment-10 to 50°C (14 to 122°F); RH max 95% non-condensing
Weight1 kg (2.2 lbs.)
Ordering InformationThe HI-8931 series is supplied with mounting brackets and instructions.