Instrumentation · Engineering · Package · PLC
0755-82221901 sales@ainstru.com

SG66.ACRBRALAMX

SG66.ACRBRALAMX
Product family: Tuning fork level switch
Tuning fork level switch
VEGA SG66.ACRBRALAMX
Tuning fork level switch;Scope Europe;Approvals ATEX II 1G, 1/2G, II 2G Ex ia IIC T6...T1 Ga, Ga/Gb, Gb;Version / Material with tube extension / 316L, Inconel 718 (2.4668), Alloy C22 (2.4602);Process fitting / Material Flange DN50 PN40 Form V13, DIN2501 / 316/316L;Second line of defense / Process temperature with / -196...+450°C;Electronics Two-wire (8/16 mA) 9.6 ... 35 V DC with SIL qualification;Housing / Protection Aluminium single chamber / IP66/IP67;Cable entry / Connect

Order Code:SG66.ACRBRALAMX

Name:Tuning fork level switch

Configuration

CodeNameOrderSpecification
020ScopeAEurope
030ApprovalsCATEX II 1G, 1/2G, II 2G Ex ia IIC T6...T1 Ga, Ga/Gb, Gb
040Version / MaterialRwith tube extension / 316L, Inconel 718 (2.4668), Alloy C22 (2.4602)
060Process fitting / MaterialBRFlange DN50 PN40 Form V13, DIN2501 / 316/316L
070Second line of defense / Process temperatureAwith / -196...+450°C
080ElectronicsLTwo-wire (8/16 mA) 9.6 ... 35 V DC with SIL qualification
090Housing / ProtectionAAluminium single chamber / IP66/IP67
120Cable entry / ConnectionMM20x1.5 / Cable gland PA black (ø5-9mm)
150CertificatesXNo

Configuration Explained

This is an SG66 vibrating level switch, extended pipe version, 316L and Inconel materials, with ATEX intrinsic safety approval and SIL assessment, directly selectable for safety loops, DN50 PN40 Form V13 flange process connection, according to DIN2501, 316/316L, resistant to high temperature and corrosion, two-wire 8/16 mA, 9.6 to 35 VDC, suitable for SIL interlock level detection in hazardous areas.

10 models · click to collapse