Technical Data
CompareDisinfection
| Measuring Principle | |
| Application | Ensuring reliable disinfection in drinking water Process water Dosing disinfectant efficiently in pool water Detect the absence or presence of free chlorine in Utilities Guarantee food safety and provide hygienic packaging and bottling |
| Characteristic | Amperometric measurement of dissolved free chlorine |
| Measuring range | Trace: 0 to 5 mg/l HOCl Standard: 0 to 20 mg/l HOCl High: 0 to 200 mg/l HOCl |
| Measuring method | Closed, membrane covered measuring cell Reduction of free chlorine at the cathode |
| Design | Closed amperometric 2-electrode measuring cell with PVDF membrane |
| Material | Sensor shaft: POM Membrane: PVDF Membrane cap: PVDF Sealing ring: FKM |
| Dimension | Diameter: 25 mm (0.98 inch) Length: 161 mm (6.34 inch) |
| Process temperature | 0 to 55 °C (32 to 130 °F), non-freezing |
| Process pressure | Max. 1 bar (max. 14.5 psi) |
| Temperature sensor | 10k NTC integrated (Memosens) |
| Connection | Inductive, digital connection head with Memosens |
The Memosens CCS51D free chlorine sensor is robust and requires low maintenance. The sensor performs high-precision measurement with high long-term stability in drinking water, pool water and process water; it reliably monitors the disinfection process even at low flow rates. The short response time of the free chlorine sensor ensures efficient process control and process safety. The CCS51D uses Memosens digital technology for the highest process and data integrity, and is easy to operate.
Benefits
A suitable sensor for every application: from trace measurement up to a free chlorine concentration of no more than 200 mg/l.
Short response time (t90 < 25 seconds) with high-precision indication of process status, enabling prompt action in response to process changes and efficient process control.
Greater process safety: accurate and long-term stable measurement enables permanent process monitoring, with flexible on-demand adjustment of the disinfectant concentration.
The fluorescence-based sensor requires low maintenance and, compared with colorimetric measuring systems, significantly reduces the operating costs of the measuring point.
Fast and convenient sensor replacement for longer uptime: laboratory pre-calibrated sensor, plug-and-play on site.
Used together with the Liquiline multiparameter transmitter, it can simultaneously measure other relevant water analysis parameters such as pH and ORP.
Applications
The Memosens CCS51D free chlorine sensor meets the requirements of skid manufacturers and end users. It reliably measures:
Drinking water: ensures reliable disinfection
Food: ensures food safety and hygienic bagged and bottled products
Utilities: detects the presence of free chlorine
Pool water: efficient dosing of disinfectant
Spare Parts & Accessories 7
7 spare parts · click to collapse
| Order code | Description | |
|---|---|---|
| CCV05- | Maintenance Kit CCV05Memosens CCSxxD/fixed cable sensor CCSxx | Enquire |
| 71372025 | CCA250 adapter kit CCS5x + CCS5xD | Details |
| 71372026 | CYA112 adapter kit CCS5x + CCS5xD | Details |
| 71372027 | CCA151 adapter kit CCS5x + CCS5xD, incl.: retaining ring, thrust ring, sealing ringContent: Clamp ring, thrust ring, + sealing | Details |
| 71554885 | Adapter kit CCS5x(D/E) for CYA27-xxxB* | Details |
| COY8- | Zero-Point Gel COY8Zero point: Verification, calibration, adjustment at zero point of oxygen and disinfection sensors ::Amperometric and optical sensors ::12, 25 and 40mm diameter ::Application in the lab, in the field | Enquire |
| 71257946 | Handheld DPD Colorimetric Calibrator PF-3colorimetric measurement of free and total chlorine 0,05 - 6mg/l Disinfection, drinking and process water hand held photometer, IP67-graded, with cuvettes, DPD, according to ISO 7393 delivery in plastic case, test kit for free and total chlorine included hand-held photometer for calibration and verification of disinfection loops | Details |
Configurator / Comparison
A
Measurement principle video
Click to playSource: Endress+Hauserpublic information from the website
Manuals & Documents 4
All documents for this modelCase Studies
Municipal Wastewater Treatment · sterilize — Application Case
Customer Profile
The typical setting in Municipal Wastewater Treatment is the inlet, biological and outlet stages of a municipal plant. The measuring point is sterilize; the focus is monitoring and controlling disinfectant dosing and efficacy.
Key Difficulties
Conditions are high solids and corrosive fractions, with large diurnal flow swings and, on top of that, effluent parameters drift and probes foul with sludge and biofilm, which a standard configuration cannot handle for long. The design therefore starts with matching monitoring points to the disinfection route (chlorine, UV, ozone).
Implementation
The scope ran through the analyser range: selecting as part of a complete water-analysis system. Technically it hinges on matching monitoring points to the disinfection route (chlorine, UV, ozone), and on these requirements: stable compliance with Grade 1A discharge limits and online data reporting.
Customer Benefit
In practice this means on-demand dosing, lowering both by-products and cost, which cut the workload on the site maintenance team.
Food & Beverage · sterilize — Application Case
Project Background
The project covers dosing, pasteurising, filling and CIP stages. The work centres on sterilize and the core task is monitoring and controlling disinfectant dosing and efficacy.
Operating Challenges
The medium and duty are characterised by syrups, dairy and beverages that scale easily, under strict hygienic requirements, and frequent cleaning demands instruments that withstand hot CIP/SIP caustic cycles. So sterilize cannot be specified generically — it calls for matching monitoring points to the disinfection route (chlorine, UV, ozone).
Solution
The Ainstru engineering team worked through the analyser range: selecting as part of a complete water-analysis system. The configuration involves matching monitoring points to the disinfection route (chlorine, UV, ozone), with these requirements in view: food-safety and hygienic design per 3-A / EHEDG.
Results
Since start-up the system has run steadily; the practical result is on-demand dosing, lowering both by-products and cost.
Chemical & Pharmaceutical · sterilize — Application Case
Project Overview
The site is reactors, metering vessels and finished-product tanks. The customer wanted sterilize properly configured on the existing plant, with the aim of monitoring and controlling disinfectant dosing and efficacy.
Technical Challenges
What actually causes trouble is highly corrosive media with solvents and crystallisation, partly in explosive atmospheres, and corrosion plus Ex protection shortens instrument life and makes downtime costly. All of this means the sterilize configuration has to involve matching monitoring points to the disinfection route (chlorine, UV, ozone).
Configuration
Supply and installation were organised through the analyser range: selecting as part of a complete water-analysis system. On site this meant matching monitoring points to the disinfection route (chlorine, UV, ozone), checked line by line against: Ex certification and GMP traceability of records.
Performance
After commissioning the outcome is on-demand dosing, lowering both by-products and cost, and the readings are now used for process tuning.
Power & Energy · sterilize — Application Case
Site Conditions
This is a Power & Energy customer whose plant is at boiler feedwater, turbine condensate and FGD/DeNOx systems. The main task was monitoring and controlling disinfectant dosing and efficacy.
The Problem
The difficulty lies in high temperature and pressure with both steam and saline water; at the same time drift under high temperature and pressure, with very costly unplanned outages. Specification therefore means matching monitoring points to the disinfection route (chlorine, UV, ozone).
What We Did
We took a analyser range approach — selecting as part of a complete water-analysis system. Delivery was built around matching monitoring points to the disinfection route (chlorine, UV, ozone), with point-by-point checks on: compliance with power-industry codes and unit availability targets.
Operating Outcome
In service the system performs as intended — on-demand dosing, lowering both by-products and cost, with routine maintenance falling noticeably.
Related Products
Endress+HauserChloromax CCS 142D
Endress+HauserFLOWFIT-W CCA250
Endress+HauserMemosens CCS120D
Endress+HauserLiquisys M CCM223
Endress+HauserAnalog free chlorine sensor CCS51
Endress+HauserChlorine sensor cell CCS140
Endress+HauserLiquisys M CCM253
Endress+Hauser