TMT111 iTEMP TMT111,Transmitter DIN rail PCPDiscontinued

TMT111 iTEMP TMT111,Transmitter DIN rail PCP
iTEMP TMT111,Transmitter DIN rail PCPDiscontinued
Unsurpassed reliability, accuracy and long-term stability in critical processes over all industries. The configurable transmitter not only transfers converted signals from resistance thermometers (RTD) and thermocouples (TC), it also transfers resistance and voltage signals. The standardized output signal is a 4 to 20 mA signal. Swift and easy operation, visualization and maintenance by PC using operating software. Space-saving DIN rail mounting as per IEC 60715 (housing width: 12.6 mm)
Compare

Temperature transmitters

Measuring Principle
Input 1 x RTD, TC, Ohm, mV
Output 1 x analog 4...20 mA
Auxiliary power supply 12...35 V DC (standard-version)
12...30 V DC (Ex-version)
Communication pc-programmable
Installation DIN rail
Accuracy (Pt100, -50...200 °C) <= 0,2 K
(Pt100, -58...392 °F) <= 0,4 °F
Galvanic isolation yes
Certification UL rec. Comp
ATEX II2(1)G Ex ia IIC T4/T5/T6
FM+CSA IS, NI I/1+2/ABCD
FM IS, NI I/1+2/ABCD
CSA IS, NI I/1+2/ABCD

Superior reliability, accuracy and long-term stability in the critical process stages of all industries. The configurable transmitter converts signals into not only resistance thermometer (RTD) and thermocouple (TC) signals, but also resistance and voltage signals. The standard output signal is 4...20 mA. 

Fast and simple operation, visualization and maintenance using a commissioning tool on a PC. Space-saving DIN rail mounting in accordance with IEC 60715 (housing width: 12.6 mm)

 

Benefits

  • Fault signaling for sensor open circuit or short circuit, presettable in accordance with NAMUR NE43

  • UL-listed components in accordance with UL 3111-1

  • CSA general-purpose approval

  • Meets EMC requirements in accordance with NAMUR NE21

  • Explosion protection certificates: ATEX Ex ia, CSA IS, FM IS

  • 2 kV electrical isolation (input/output)

  • Output simulation for fast and simple testing of the measuring loop

 

Application areas

  • PC-programmable (PCP) DIN rail temperature transmitter for converting various input signals into a 4...20 mA analog output signal

  • Can be connected to resistance thermometer (RTD), thermocouple (TC), resistance (Ω) and voltage (mV) signals

  • Device configuration via a PC with the configuration kit and ReadWin 2000 PC software

  • Installed on a TH35 DIN rail in accordance with IEC 60715

 

Spare Parts & Accessories 1

1 spare parts · click to collapse
Order codeDescription
TXU10-Instrument Commissioning Kit TXU10用于可以PC编程调试的设备 程序设置+用于带USB接口的PC的连接线Enquire

Configurator / Comparison

ConfigureEnter a product model to configure
CompareEnter the product models to compare — up to three products

   

   

 

 

Source: public information from the Endress+Hauser website

Measuring principle video

Click to play
All documents for this model
7 documents · click to expand
BA

操作手册 iTEMP® TMT111 Chinese

Rev. 1313 8 pages
Preview
BA

iTEMP® TMT111, DIN rail Operating Instructions English

Rev. 1418 32 pages
Preview
BA

iTEMP® TMT111, DIN rail Operating Instructions English

Rev. 1313 29 pages
Preview
BA

Operating Instructions iTEMP® TMT111, DIN rail English

Rev. 1108 27 pages
Preview
TI

技术资料 iTEMP® TMT111 Chinese

Rev. 0111 12 pages
Preview
TI

Technical Information iTEMP® TMT111, DIN rail English

Rev. 1108 10 pages
Preview
TI

Technical Information iTEMP® TMT111, DIN rail English

Rev. 0218 12 pages
Preview
Municipal Wastewater Treatment

Municipal Wastewater Treatment · Temperature transmitter — Application Case

Site Conditions

This is a Municipal Wastewater Treatment customer whose plant is at the inlet, biological and outlet stages of a municipal plant. The main task was converting RTD or thermocouple signals into a standard current output.

The Problem

The difficulty lies in high solids and corrosive fractions, with large diurnal flow swings; at the same time effluent parameters drift and probes foul with sludge and biofilm. Specification therefore means choosing integral or remote versions by ambient, Ex zone and mounting.

What We Did

We took a temperature range approach — temperature solution matched to measuring point and response needs. Delivery was built around choosing integral or remote versions by ambient, Ex zone and mounting, with point-by-point checks on: stable compliance with Grade 1A discharge limits and online data reporting.

Operating Outcome

In service the system performs as intended — better noise immunity and much smaller transmission error, with routine maintenance falling noticeably.

Food & Beverage

Food & Beverage · Temperature transmitter — Application Case

Application Context

dosing, pasteurising, filling and CIP stages is a typical Food & Beverage duty. The project started from Temperature transmitter, focusing on converting RTD or thermocouple signals into a standard current output.

Process Constraints

frequent cleaning demands instruments that withstand hot CIP/SIP caustic cycles, and syrups, dairy and beverages that scale easily, under strict hygienic requirements only amplify it. The Temperature transmitter specification must therefore cover choosing integral or remote versions by ambient, Ex zone and mounting.

Delivery Approach

Delivery was handled as the temperature range — temperature solution matched to measuring point and response needs. Execution centred on choosing integral or remote versions by ambient, Ex zone and mounting, together with food-safety and hygienic design per 3-A / EHEDG.

Field Results

Operation shows the benefit clearly — better noise immunity and much smaller transmission error, with confidence in this measuring point improving markedly.

Chemical & Pharmaceutical

Chemical & Pharmaceutical · Temperature transmitter — Application Case

Customer Profile

The typical setting in Chemical & Pharmaceutical is reactors, metering vessels and finished-product tanks. The measuring point is Temperature transmitter; the focus is converting RTD or thermocouple signals into a standard current output.

Key Difficulties

Conditions are highly corrosive media with solvents and crystallisation, partly in explosive atmospheres and, on top of that, corrosion plus Ex protection shortens instrument life and makes downtime costly, which a standard configuration cannot handle for long. The design therefore starts with choosing integral or remote versions by ambient, Ex zone and mounting.

Implementation

The scope ran through the temperature range: temperature solution matched to measuring point and response needs. Technically it hinges on choosing integral or remote versions by ambient, Ex zone and mounting, and on these requirements: Ex certification and GMP traceability of records.

Customer Benefit

In practice this means better noise immunity and much smaller transmission error, which cut the workload on the site maintenance team.

Power & Energy

Power & Energy · Temperature transmitter — Application Case

Project Background

The project covers boiler feedwater, turbine condensate and FGD/DeNOx systems. The work centres on Temperature transmitter and the core task is converting RTD or thermocouple signals into a standard current output.

Operating Challenges

The medium and duty are characterised by high temperature and pressure with both steam and saline water, and drift under high temperature and pressure, with very costly unplanned outages. So Temperature transmitter cannot be specified generically — it calls for choosing integral or remote versions by ambient, Ex zone and mounting.

Solution

The Ainstru engineering team worked through the temperature range: temperature solution matched to measuring point and response needs. The configuration involves choosing integral or remote versions by ambient, Ex zone and mounting, with these requirements in view: compliance with power-industry codes and unit availability targets.

Results

Since start-up the system has run steadily; the practical result is better noise immunity and much smaller transmission error.