Technical Data
CompareTemperature transmitters
| Measuring Principle | |
| Input | 1 x RTD, TC, Ohm, mV |
| Output | 1 x analog 4...20 mA |
| Auxiliary power supply | 12...35 V DC (standard-version) 12...30 V DC (Ex-version) |
| Communication | HART-protocol |
| Installation | DIN rail |
| Accuracy | (Pt100, -50...200 °C) <= 0,2 K (Pt100, -58...392 °F) <= 0,4 °F |
| Galvanic isolation | yes |
| Certification | UL rec. Comp marine approval GOST Metrology FM IS,NI,Class I,Div.1+2,Group ABCD CSA IS,NI,Class I,Div.1+2,Group ABCD ATEX II2(1)G Ex ia[ia Ga] IIC T6 Gb ATEX II3G Ex nA IIC T6 FM+CSA IS,NI,Class I,Div.1+2,Group ABCD CSA General Purpose IECEx Ex ia IIC T6/T5/T4 NEPSI Ex nA IIC T4-T6 |
Superior reliability, accuracy and long-term stability in critical processes in all industries. The configurable transmitter not only digitally converts resistance thermometer (RTD) and thermocouple (TC) signals, but can also convert resistance and voltage signals via HART® communication. Commissioning tools installed on a personal computer enable fast, simple operation, display and maintenance. Mounted on a DIN rail complying with IEC 60715 (housing width: 22.5 mm).
Advantages
Universal configuration via HART® communication
High-precision measurement over the entire ambient temperature range
Fault signal on sensor wire break or short circuit, in accordance with NAMUR NE43
Meets EMC requirements in accordance with NAMUR NE21, CE approval
Explosion protection certificates: ATEX Ex, CSA IS, FM IS
Galvanic isolation
Complies with SIL2 approval
Application areas
The HART® communication temperature transmitter is used to convert different input signals into a 4...20 mA analog output signal
Input: resistance thermometer (RTD), thermocouple (TC), resistance (Ω) and voltage (mV)
HART® communication, operating front-end or panel devices using a handheld (DXR275, DXR375) or personal computer (e.g. ReadWin 2000 or FieldCare)
Spare Parts & Accessories 7
7 spare parts · click to collapse
| Order code | Description | |
|---|---|---|
| 51006248 | terminal blockTerminal plug-in 4pole SMSTB2,5 printed | Details |
| 51006249 | terminal blockTerminal plug-in 4pole SMSTB2,5 printed | Details |
| 51006250 | terminal blockTerminal plug-in 2pole RM5 printed -/+ | Details |
| 51006251 | terminal blockTermin plug-in 2pole RM5 printed -/+ | Details |
| 71402350 | Panel mounting accessoryfor RMA42x/RMx621/RTA421/RN221N/TMT12x | Details |
| FXA195- | Communication interface FXA195Modem to connect HART field devices to a computer via USB. Commissioning of field devices with software tool. :: To connect to a intrinsically safe signal circuit. :: SIL2, IEC61508. | Enquire |
| READWIN- | Readwin 2000 Commissioning Package READWINReadwin 2000 Operation + Read. software | Enquire |
Configurator / Comparison
Accessories / Spare parts
Source:Endress+Hauserpublic information from the website
Measuring principle video
Click to playManuals & Documents 9
All documents for this model9 documents · click to expand
Operating manual iTEMP HART Communication English
Operating Manuals ReadWin 2000 (GB) English
BA155R Operating Instructions for TMT 122 Version 07.03 English
BA155R Operating Instructions for TMT 122 Version 07.03 English
ReadWin® Quick Setup English
Operating Manuals ReadWin 2000 (GB) English
技术资料 iTEMP® HART® TMT122 Chinese
iTEMP HART® TMT122 DIN rail English
iTEMP® TMT122 HART® DIN rail Technical information English
Case Studies
Municipal Wastewater Treatment · Temperature transmitter — Application Case
Site Conditions
This is a Municipal Wastewater Treatment customer whose plant is at the inlet, biological and outlet stages of a municipal plant. The main task was converting RTD or thermocouple signals into a standard current output.
The Problem
The difficulty lies in high solids and corrosive fractions, with large diurnal flow swings; at the same time effluent parameters drift and probes foul with sludge and biofilm. Specification therefore means choosing integral or remote versions by ambient, Ex zone and mounting.
What We Did
We took a temperature range approach — temperature solution matched to measuring point and response needs. Delivery was built around choosing integral or remote versions by ambient, Ex zone and mounting, with point-by-point checks on: stable compliance with Grade 1A discharge limits and online data reporting.
Operating Outcome
In service the system performs as intended — better noise immunity and much smaller transmission error, with routine maintenance falling noticeably.
Food & Beverage · Temperature transmitter — Application Case
Application Context
dosing, pasteurising, filling and CIP stages is a typical Food & Beverage duty. The project started from Temperature transmitter, focusing on converting RTD or thermocouple signals into a standard current output.
Process Constraints
frequent cleaning demands instruments that withstand hot CIP/SIP caustic cycles, and syrups, dairy and beverages that scale easily, under strict hygienic requirements only amplify it. The Temperature transmitter specification must therefore cover choosing integral or remote versions by ambient, Ex zone and mounting.
Delivery Approach
Delivery was handled as the temperature range — temperature solution matched to measuring point and response needs. Execution centred on choosing integral or remote versions by ambient, Ex zone and mounting, together with food-safety and hygienic design per 3-A / EHEDG.
Field Results
Operation shows the benefit clearly — better noise immunity and much smaller transmission error, with confidence in this measuring point improving markedly.
Chemical & Pharmaceutical · Temperature transmitter — Application Case
Customer Profile
The typical setting in Chemical & Pharmaceutical is reactors, metering vessels and finished-product tanks. The measuring point is Temperature transmitter; the focus is converting RTD or thermocouple signals into a standard current output.
Key Difficulties
Conditions are highly corrosive media with solvents and crystallisation, partly in explosive atmospheres and, on top of that, corrosion plus Ex protection shortens instrument life and makes downtime costly, which a standard configuration cannot handle for long. The design therefore starts with choosing integral or remote versions by ambient, Ex zone and mounting.
Implementation
The scope ran through the temperature range: temperature solution matched to measuring point and response needs. Technically it hinges on choosing integral or remote versions by ambient, Ex zone and mounting, and on these requirements: Ex certification and GMP traceability of records.
Customer Benefit
In practice this means better noise immunity and much smaller transmission error, which cut the workload on the site maintenance team.
Power & Energy · Temperature transmitter — Application Case
Project Background
The project covers boiler feedwater, turbine condensate and FGD/DeNOx systems. The work centres on Temperature transmitter and the core task is converting RTD or thermocouple signals into a standard current output.
Operating Challenges
The medium and duty are characterised by high temperature and pressure with both steam and saline water, and drift under high temperature and pressure, with very costly unplanned outages. So Temperature transmitter cannot be specified generically — it calls for choosing integral or remote versions by ambient, Ex zone and mounting.
Solution
The Ainstru engineering team worked through the temperature range: temperature solution matched to measuring point and response needs. The configuration involves choosing integral or remote versions by ambient, Ex zone and mounting, with these requirements in view: compliance with power-industry codes and unit availability targets.
Results
Since start-up the system has run steadily; the practical result is better noise immunity and much smaller transmission error.
Related Products
Endress+HauseriTEMP TMT72, Transmitter HART
Endress+HauseriTEMP TMT182, Head Transmitter HART
Endress+HauseriTEMP TMT82, Transmitter HART
Endress+HauseriTEMP TMT71, Transmitter 4-20mA
Endress+HauseriTEMP TMT80, Head Transmitter
Endress+HauseriTEMP TMT31, Transmitter 4-20mA
Endress+HauseriTEMP TMT142, Field Transmitter HART
Endress+Hauser