Instrumentation · Engineering · Package · PLC
0755-82221901 sales@ainstru.com

TMT82-1KMX0/160

TMT82-1KMX0/160
Product family: iTEMP TMT82, Transmitter HART
iTEMP TMT82, Transmitter HARTIn Stock (8)
Endress+Hauser TMT82-1KMX0/160
iTEMP TMT82, Transmitter HART;Approval NEPSI Ex ia IIC T6 Ga;Communication/Output Signal HART; 1x 4-20mA;Electrical Connection Screw terminals, housing form B, DIN EN 50446;Field Housing W/o, mounting set DIN terminal head;Configuration Universal Input Ch1: RTD 3-wire, Ch2: RTD 3-wire;Sensor Type Input 1 Pt100, IEC60751 (a=0.00385), -200...+850oC, min. span 10K;Sensor Type Input 2 Pt100, IEC60751 (a=0.00385);Input/Interconnection Sensor backup; PV=CH1(or CH2);Marking Tagging

Order Code:TMT82-1KMX0/160

Corresponding ext. order code:TMT82-NAA2AB3A1A1A5+Z1

Name:iTEMP TMT82, Transmitter HART

Configuration

CodeNameOrderSpecification
010ApprovalNANEPSI Ex ia IIC T6 Ga
020Communication; Output SignalAHART; 1x 4-20mA
030Electrical Connection2Screw terminals, housing form B, DIN EN 50446
040Field HousingAW/o, mounting set DIN terminal head
050Configuration Universal InputB3Ch1: RTD 3-wire, Ch2: RTD 3-wire
060Sensor Type Input 1A1Pt100, IEC60751 (a=0.00385), -200...+850oC, min. span 10K
070Sensor Type Input 2A1Pt100, IEC60751 (a=0.00385)
080Input; InterconnectionA5Sensor backup; PV=CH1(or CH2)
895MarkingZ1Tagging (TAG), metal

Configuration Explained

This is a TMT82 dual-channel temperature transmitter, HART protocol, with NEPSI intrinsically safe approval, can be installed in hazardous areas, 1 x 4-20mA HART output, both channels with Pt100 three-wire input, hot backup, if one probe has a problem the other takes over, output selectable between the two channels, replace the probe without stopping the process, screw terminal wiring, DIN standard transmitter head kit mounting, with metal tag plate, suitable for redundant temperature measurement at critical chemical measuring points.