TMT112 iTEMP TMT112,Transmitter DINrail HARTDiscontinued

TMT112 iTEMP TMT112,Transmitter DINrail HART
iTEMP TMT112,Transmitter DINrail HARTDiscontinued
Unsurpassed reliability, accuracy and long-term stability in critical processes over all industries. The configurable transmitter not only transfers converted signals from resistance thermometers (RTD) and thermocouples (TC), it also transfers resistance and voltage signals using HART® communication. Swift and easy operation, visualization and maintenance by PC using operating software. Space-saving DIN rail mounting according to IEC 60715 (housing width: 12.6 mm).
Compare

Temperature transmitters

Measuring Principle
Input 1 x RTD, TC, Ohm, mV
Output 1 x analog 4...20 mA
Auxiliary power supply 12...35 V DC (standard-version)
12...30 V DC (Ex-version)
Communication HART
Installation DIN rail
Accuracy (Pt100, -50...200 °C) <= 0,2 K
(Pt100, -58...392 °F) <= 0,4 °F
Galvanic isolation yes
Certification UL rec. Com
FM IS,NI,Class I,Div.1+2,Group ABCD
CSA IS,NI,Class I,Div.1+2,Group ABCD
ATEX II2(1)G EEx ia IIC T4/T5/T6
ATEX II3G Ex nA IIC T6
CSA General Purpose

Outstanding reliability, accuracy and long-term stability in critical processes in all industries. The configurable transmitter not only converts resistance thermometer (RTD) and thermocouple (TC) signals digitally, but also converts resistance and voltage signals via HART® communication. Quick and simple operation, display and maintenance using the configuration tools installed on a personal computer. Space-saving DIN rail mounting, rail conforming to IEC 60715 (housing width: 12.6 mm).

 

Benefits

Universal configuration via HART® communication

High-accuracy measurement over the entire ambient temperature range

Fault signal in the event of sensor open-circuit or short-circuit, configured in accordance with NAMUR NE43

Meets EMC requirements in accordance with NAMUR NE21, CE approval

Explosion protection certificates: ATEX Ex, CSA IS, FM IS

Galvanic isolation

SIL2 certified

 

Application

The HART® temperature transmitter is used to convert various input signals into a 4...20 mA analog output signal

Input:

 

Resistance thermometer (RTD)

Thermocouple (TC)

Resistance (Ω)

Voltage (mV)

HART® communication for operating head-mounted or DIN rail devices using a handheld communicator (DXR275, DXR375) or a personal computer (e.g. ReadWin 2000 or FieldCare)

Mounted on a DIN rail conforming to IEC 60715

Spare Parts & Accessories 2

2 spare parts · click to collapse
Order codeDescription
FXA195-Communication interface FXA195Modem to connect HART field devices to a computer via USB. Commissioning of field devices with software tool. :: To connect to a intrinsically safe signal circuit. :: SIL2, IEC61508.Enquire
READWIN-Readwin 2000 Commissioning Package READWINReadwin 2000 Operation + Read. softwareEnquire

Configurator / Comparison

ConfigureEnter a product model to configure
CompareEnter the product models to compare — up to three products

   

   

 

 

Source:Endress+Hauserwebsite public information

Measuring principle video

Click to play
All documents for this model
7 documents · click to expand
BA

iTEMP TMT112 Operating Instructions English

Rev. 0119 36 pages
Preview
TI

iTEMP® TMT112 HART® DIN rail Technical Information Chinese

HART Rev. 1418 8 pages
Preview
TI

技术资料 iTEMP® HART® TMT112 Chinese

HART Rev. 1310 12 pages
Preview
TI

iTEMP TMT112 HART® DIN rail English

HART Rev. 1519 8 pages
Preview
TI

iTEMP® TMT112 HART® DIN rail Technical Information English

HART Rev. 1418 8 pages
Preview
TI

iTEMP® TMT112 HART® DIN rail Technical Information English

HART Rev. 1310 12 pages
Preview
TI

Technical information iTEMP HART DIN rail TMT112 English

HART 10 pages
Preview
Municipal Wastewater Treatment

Municipal Wastewater Treatment · Temperature transmitter — Application Case

Site Conditions

This is a Municipal Wastewater Treatment customer whose plant is at the inlet, biological and outlet stages of a municipal plant. The main task was converting RTD or thermocouple signals into a standard current output.

The Problem

The difficulty lies in high solids and corrosive fractions, with large diurnal flow swings; at the same time effluent parameters drift and probes foul with sludge and biofilm. Specification therefore means choosing integral or remote versions by ambient, Ex zone and mounting.

What We Did

We took a temperature range approach — temperature solution matched to measuring point and response needs. Delivery was built around choosing integral or remote versions by ambient, Ex zone and mounting, with point-by-point checks on: stable compliance with Grade 1A discharge limits and online data reporting.

Operating Outcome

In service the system performs as intended — better noise immunity and much smaller transmission error, with routine maintenance falling noticeably.

Food & Beverage

Food & Beverage · Temperature transmitter — Application Case

Application Context

dosing, pasteurising, filling and CIP stages is a typical Food & Beverage duty. The project started from Temperature transmitter, focusing on converting RTD or thermocouple signals into a standard current output.

Process Constraints

frequent cleaning demands instruments that withstand hot CIP/SIP caustic cycles, and syrups, dairy and beverages that scale easily, under strict hygienic requirements only amplify it. The Temperature transmitter specification must therefore cover choosing integral or remote versions by ambient, Ex zone and mounting.

Delivery Approach

Delivery was handled as the temperature range — temperature solution matched to measuring point and response needs. Execution centred on choosing integral or remote versions by ambient, Ex zone and mounting, together with food-safety and hygienic design per 3-A / EHEDG.

Field Results

Operation shows the benefit clearly — better noise immunity and much smaller transmission error, with confidence in this measuring point improving markedly.

Chemical & Pharmaceutical

Chemical & Pharmaceutical · Temperature transmitter — Application Case

Customer Profile

The typical setting in Chemical & Pharmaceutical is reactors, metering vessels and finished-product tanks. The measuring point is Temperature transmitter; the focus is converting RTD or thermocouple signals into a standard current output.

Key Difficulties

Conditions are highly corrosive media with solvents and crystallisation, partly in explosive atmospheres and, on top of that, corrosion plus Ex protection shortens instrument life and makes downtime costly, which a standard configuration cannot handle for long. The design therefore starts with choosing integral or remote versions by ambient, Ex zone and mounting.

Implementation

The scope ran through the temperature range: temperature solution matched to measuring point and response needs. Technically it hinges on choosing integral or remote versions by ambient, Ex zone and mounting, and on these requirements: Ex certification and GMP traceability of records.

Customer Benefit

In practice this means better noise immunity and much smaller transmission error, which cut the workload on the site maintenance team.

Power & Energy

Power & Energy · Temperature transmitter — Application Case

Project Background

The project covers boiler feedwater, turbine condensate and FGD/DeNOx systems. The work centres on Temperature transmitter and the core task is converting RTD or thermocouple signals into a standard current output.

Operating Challenges

The medium and duty are characterised by high temperature and pressure with both steam and saline water, and drift under high temperature and pressure, with very costly unplanned outages. So Temperature transmitter cannot be specified generically — it calls for choosing integral or remote versions by ambient, Ex zone and mounting.

Solution

The Ainstru engineering team worked through the temperature range: temperature solution matched to measuring point and response needs. The configuration involves choosing integral or remote versions by ambient, Ex zone and mounting, with these requirements in view: compliance with power-industry codes and unit availability targets.

Results

Since start-up the system has run steadily; the practical result is better noise immunity and much smaller transmission error.