FMD71 differential pressure transmitter

FMD71 differential pressure transmitter
Deltabar FMD71
The electronic differential pressure system consists of two sensors and one transmitter
Compare

Continuous / Liquids

Measuring Principle Differential pressure
Characteristic / Application Electronic differential pressure transmitter with ceramic sensor (Ceraphire) for level, volume or mass measurement in liquids.
Supply / Communication 4...20 mA HART:
12...45V DC
Exia: 12...30V DC
Accuracy 0.075% of individual sensor,
"PLATINUM" 0.05% of individual sensor
Long term stability 0.05% of URL/year of individual sensor
Ambient temperature –40...+80°C
(–40...+176°F)
Process temperature –25...+150°C
(–13...+302°F)
Process pressure / max. overpressure limit 60 bar (900 psi)
Pressure measuring range 100mbar...40bar
(1.5psi...600psi)
Process connection Threads
Flanges (DIN, ASME, JIS)
Process connection hygienic DIN11851
DIN11864-1
Tri-Clamp
DRD
Varivent
Communication 4...20 mA HART
Certificates / Approvals ATEX, FM, CSA, CSA C/US, IEC Ex, NEPSI, INMETRO
Design approvals NACE MR0175
EN10204-3.1
Hygienic approvals FDA
3A
Options 4-line digital display
SS- or Aluminium housing
Application limits Use Software Applicator Sizing Electronic DP

Pressure

Measuring Principle Differential pressure
Characteristic Electronic differential pressure transmitter with ceramic sensor (Ceraphire) for level, volume or mass measurement in liquids.
Supply voltage 4...20 mA HART:
12...45V DC (Non Ex)
Ex ia: 12...30V DC
Reference Accuracy 0.075% of individual sensor,
"PLATINUM" 0.05% of individual sensor
Long term stability 0.05% of URL/year of individual sensor
Process temperature –25...+150°C
(–13...+302°F)
Ambient temperature –40...+80°C
(–40...+176°F)
Measuring cell 100 mbar...40 bar
(1.5 psi...600 psi)
Vacuum resistance 0 mbar
Max. Turn down 100 : 1
Max. overpressure limit 60 bar (900 psi)
Process connection Threads
Flansch (DIN, ASME, JIS)
Process connection hygienic DIN11851
DIN11864-1
Tri-Clamp
DRD
Varivent
Material process membrane Ceramic
316L, AlloyC
Material gasket Viton, Kalrez, EPDM, NBR, Silicone
Fill fluid Silicone Oil
Material housing Die-cast aluminum
Stainless steel
Communication 4...20 mA HART
Certificates / Approvals ATEX, FM, CSA, IECEx, NEPSI, INMETRO, UK Ex
Design approvals NACE MR0175,
EN10204-3.1,
Hygienic approvals EHEDG,
3A

The electronic differential pressure transmitter Deltabar FMD71 is a differential pressure system consisting of two sensors and one transmitter, used for level, volume or mass measurement of liquids in pressurized tanks or distillation columns/evaporators. One sensor measures the static pressure (high pressure) and the other measures the top pressure (low pressure). Based on these two digital pressure values, the transmitter calculates the level value (electronic differential pressure). The electronic differential pressure measuring system eliminates the problems that occur with conventional differential pressure measurement.

 

Advantages

The dry Ceraphire measuring cell is fully resistant to vacuum, corrosion and abrasion

Eliminates conventional mechanical problems, providing higher process suitability and reliability

The new electronic differential pressure system structure and design minimize safety risks

Minimized operating costs thanks to reduced installation, maintenance and downtime and lower spare part requirements

Multivariable level measurement: based on HART communication, measures differential pressure, top pressure and sensor temperature of the same system

Continuously indicates the health of the entire system via HART diagnostics

High repeatability and long-term stability

 

Areas of application

For level, volume or mass measurement of liquids in pressurized tanks or distillation columns/evaporators.

 

Process connections: thread, flange, flush-mounted hygienic connections

Temperature: –25...+150°C (–13...+302°F), optional 350°C (662°F)

Measuring range: 100mbar...40bar (1.5...600psi)

Measurement accuracy: up to ±0.05% for a single sensor, up to ±0.07% for the system

International explosion protection and hygienic approvals

Spare Parts & Accessories 64

64 spare parts · click to collapse
Order codeDescription
71186149Seal ring assemblyConsists of: O-ring 43.62x2.62 EPDM/PTFE, 5pcs. Usage: FMD71/FMD72.Details
71290825Grounding terminalConsists of: spring washer, screw, earth handle, clamp. Usage: housing T14/T15/T17, FMB70, FMD71/FMD72/ FMD77/FMD78, PMC71, PMP71/PMP75, PMD70/PMD75. Housing F30/F31, FMB50/FMB51/FMB52/ FMB53, PMC51, PMD55, PMP51/PMP55.Details
52024110key housingfor external operation consists of: push button, cover + screws colour: dark greyDetails
71111056Atmospheric compensation filter portConsists of: Vent screw 304. Pressure compensation filter. O-ring EPDM, protection lid. Usage: FMB50, FMB51, FMB52, FMB53, FMD71, FMD72, FMD76, FMD77, FMD78, FMR60B, FMR62B, FMR63B, FMR66B, FMR67B, PMC51, PMC71, PMD70, PMD75, PMP71, PMP75, PMP51, PMP55.Details
71186150Atmospheric compensation filter portPressure compensation plug, stainless steel. Sensor housing aluminium, stainless steel. Usage: FMD71/FMD72.Details
71186151Atmospheric compensation filter portPressure compensation plug, plastic. Sensor housing aluminium, stainless steel. Usage: FMD71/FMD72.Details
71186153FMD72 sensor cable gland, M20Consists of: cable gland M20 VA. O-ring, plug. Usage: FMD71/FMD72.Details
71186154cable entryConsists of: cable gland NPT. O-ring, plug. Usage: FMD71/FMD72.Details
71186157AdapterFor mounting over M12 plug for conduit use. Usage: FMD71/FMD72.Details
71440355Sensor connectorUsage: FMD71/FMD72.Details
71440356Transmitter M12/M20 4-pin connectorUsage: FMD71/FMD72.Details
71444959cable adapterUsage: FMD71/FMD72.Details
52020432Aluminum cover with gasketMaterial: Aluminium, coated O-ring EPDM, FDA not for EEx d/XP Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78 Deltapilot S FMB70Details
52020433Aluminum cover with gasketMaterial: Aluminium, coated O-ring EPDM, FDA for EEx d/XP Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78Details
52020433Aluminum cover with gasketMaterial: Aluminium, coated O-ring EPDM, FDA for EEx d/XP Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78Details
52028310Stainless Steel CoverMaterial: 316L O-ring EPDM, FDA individual tested, EEx d/XP Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78Details
71002774Stainless Steel CoverMaterial: 316L flat gasket VMQ, centering ring, screw not for EEx d/XP Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78 Deltapilot S FMB70Details
71002810cover with viewing windowMaterial: 316L Sight glass: mineral glass flat gasket VMQ, centering ring, screw approval 2,3,4,8,Q,W,7,8 Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78 Deltapilot S FMB70Details
71002811cover with viewing windowMaterial: 316L Sight glass: Polycarbonat PC flat gasket VMQ, centering ring, screw approval A,F,R,S,U,1,6 Cerabar S PMC71, PMP71/PMP75 Deltabar S PMD70/PMD75,FMD76/FMD77/FMD78 Deltapilot S FMB70Details
71206968Stainless Steel CoverMaterial: 316L. Sight glass: mineral glass,coated. O-ring FVMQ. Individual tested, EEx d/XP. Usage: FMD71/FMD72/FMD76/FMD77/FMD78, PMC71, PMD70/PMD75, PMP71/PMP75.Details

Configurator / Comparison

ConfigureEnter a product model to configure
CompareEnter the product models to compare — up to three products

   

   

 

 

Source:Endress+Hauserwebsite public information

Measuring principle video

Click to play
All documents for this model
6 documents · click to expand
BA

Deltabar FMD71, FMD72 操作手册 Chinese

Rev. 0515 124 pages
Preview
BA

Deltabar FMD71, FMD72 Operating Instructions English

Rev. 0617 134 pages
Preview
TI

TI 焊接接头、过程转接头和法兰 Chinese

Rev. 2726 130 pages
Preview
TI

TI Deltabar FMD71, FMD72 Chinese

Rev. 0924 68 pages
Preview
TI

TI Weld-in adapter, process adapter and flanges English

Rev. 2726 132 pages
Preview
TI

TI Deltabar FMD71, FMD72 English

Rev. 0924 68 pages
Preview
Municipal Wastewater Treatment

Municipal Wastewater Treatment · Differential Pressure Measurement — Application Case

Project Overview

The site is the inlet, biological and outlet stages of a municipal plant. The customer wanted Differential Pressure Measurement properly configured on the existing plant, with the aim of differential pressure for flow and filter monitoring.

Technical Challenges

What actually causes trouble is high solids and corrosive fractions, with large diurnal flow swings, and effluent parameters drift and probes foul with sludge and biofilm. All of this means the Differential Pressure Measurement configuration has to involve checking static pressure limit, overload margin and impulse lines.

Configuration

Supply and installation were organised through the pressure range: pressure solution matched to process pressure and temperature. On site this meant checking static pressure limit, overload margin and impulse lines, checked line by line against: stable compliance with Grade 1A discharge limits and online data reporting.

Performance

After commissioning the outcome is filters changed on pressure drop, using cartridges to their full life, and the readings are now used for process tuning.

Food & Beverage

Food & Beverage · Differential Pressure Measurement — Application Case

Site Conditions

This is a Food & Beverage customer whose plant is at dosing, pasteurising, filling and CIP stages. The main task was differential pressure for flow and filter monitoring.

The Problem

The difficulty lies in syrups, dairy and beverages that scale easily, under strict hygienic requirements; at the same time frequent cleaning demands instruments that withstand hot CIP/SIP caustic cycles. Specification therefore means checking static pressure limit, overload margin and impulse lines.

What We Did

We took a pressure range approach — pressure solution matched to process pressure and temperature. Delivery was built around checking static pressure limit, overload margin and impulse lines, with point-by-point checks on: food-safety and hygienic design per 3-A / EHEDG.

Operating Outcome

In service the system performs as intended — filters changed on pressure drop, using cartridges to their full life, with routine maintenance falling noticeably.

Chemical & Pharmaceutical

Chemical & Pharmaceutical · Differential Pressure Measurement — Application Case

Application Context

reactors, metering vessels and finished-product tanks is a typical Chemical & Pharmaceutical duty. The project started from Differential Pressure Measurement, focusing on differential pressure for flow and filter monitoring.

Process Constraints

corrosion plus Ex protection shortens instrument life and makes downtime costly, and highly corrosive media with solvents and crystallisation, partly in explosive atmospheres only amplify it. The Differential Pressure Measurement specification must therefore cover checking static pressure limit, overload margin and impulse lines.

Delivery Approach

Delivery was handled as the pressure range — pressure solution matched to process pressure and temperature. Execution centred on checking static pressure limit, overload margin and impulse lines, together with Ex certification and GMP traceability of records.

Field Results

Operation shows the benefit clearly — filters changed on pressure drop, using cartridges to their full life, with confidence in this measuring point improving markedly.

Power & Energy

Power & Energy · Differential Pressure Measurement — Application Case

Customer Profile

The typical setting in Power & Energy is boiler feedwater, turbine condensate and FGD/DeNOx systems. The measuring point is Differential Pressure Measurement; the focus is differential pressure for flow and filter monitoring.

Key Difficulties

Conditions are high temperature and pressure with both steam and saline water and, on top of that, drift under high temperature and pressure, with very costly unplanned outages, which a standard configuration cannot handle for long. The design therefore starts with checking static pressure limit, overload margin and impulse lines.

Implementation

The scope ran through the pressure range: pressure solution matched to process pressure and temperature. Technically it hinges on checking static pressure limit, overload margin and impulse lines, and on these requirements: compliance with power-industry codes and unit availability targets.

Customer Benefit

In practice this means filters changed on pressure drop, using cartridges to their full life, which cut the workload on the site maintenance team.